Overview - Why
Humidify?
Air that is too dry is just
as much of a problem as air that is too wet, and in many cases, much more dangerous.
Certain industrial processes, such as box board manufacturing, are prone to fire
or explosions when moving materials in dry air builds up static electricity that
discharges in the presence of dust, VOCs and other combustibles.
Office buildings, mostly
in northern and dry climates, suffer many problems caused by dry air. Including
static electricity that ruins electronic equipment to occupant health and comfort
issues. ASHRAE Standard 62 has attempted to regulate indoor relative humidity
level (Rh) in the same way that it regulates air exchange rates. However, this
has been very controversial and has not been uniformly accepted. Therefore, some
geographic areas may have Rh standards, while others do not even mention it in
their local building codes. Progressive facility managers include humidification
systems, even though they may not be required to by code or obvious safety reasons.
Numerous studies
done by ASHRAE and other indoor air quality experts, suggest an optimum Rh range
of 40 to 60%. Dryer or wetter causes different kinds of problems, at each extreme.
See the chart below, based on ASHRAE sponsored research.

Economics
Humidification is a good
gas load, but is impossible to isolate from space heating load. Industrial processes
may need to humidify year-round, where space conditioning only ADDS humidity during
the winter months, and then only in northern climates.
To vaporize 1 pound of water,
it takes 212F - 32F = 180 + the Latent Heat of Vaporization = 970 BTUs = (970
+ 180) = 1,150 BTUs / Efficiency of the equipment.
Example: 100 pounds/hour,
direct fired gas or electric?
100 lbs x 1,150 BTUs/lbs
= 115,000 BTUs/80% Efficient = 1.4 CCF x $0.60/CCF = $0.86/Hour to operate.
Electric 115,000 BTUs/99%
Efficient = 116,161 BTUs/3,413 BTUs/kWh = 34 kWh x $0.08/kWh = $2.72/Hour to Operate.
Humidifiers tend
to be high maintenance items, depending on the local water quality.
Humidification
Methods and Equipment
There are several
ways to add moisture to air. The two main categories are those that add thermal
energy to vaporize the water and those that simply spray water through misting
nozzles and count on natural vaporization to do the rest. The best method will
depend on how much water needs to be vaporized how quickly, and what equipment
may already be available to help distribute the moisture.
The oldest industrial
systems used existing space heating steam boilers. If there were not enough steam
system leaks to meet humidification needs, additional steam would be vented into
the space. When air handlers came along, steam injection manifolds were developed
for large scale, controlled humidification. Generally, the same steam was used
that provided space heat and perhaps ran industrial processes. However, this steam
contained boiler water treatment chemicals. During the initial days of indoor
air quality concerns, boiler chemicals became 'tabu'. In some cases, special more
environmentally chemicals were used, but in more cases, dedicated boilers were
needed. This became expensive to install, especially for small facilities, and
facilities that would otherwise not even have a boiler. This gave rise to the
electric humidification technology. The most recently developed technology is
the direct-fired gas humidification unit.
Steam
Humidification
Steam systems
are the most economical, when there is an existing boiler and the application
requires a lot of volume. Since boiler chemicals are still a concern in most commercial
applications, steam-to-steam heat exchangers have been developed. This way, the
low operating cost of the central boiler is obtained, and there is a lower first
cost than buying a dedicated boiler system. There are also chemicals that are
certified safe for humidification applications.
Direct
Fired
Direct fired natural gas
humidifiers produced steam directly. They are designed to operate with no steam
pressure build-up (other than what's needed to deliver the steam) and deal with
hard water fouling without the use of treatment chemicals. Direct fired units
are the most economical systems for large applications where there is no existing
boiler.
The first direct fired unit
was introduced by DriSteem, and is called the GTS Humidifier (Gas To Steam). It
resembles a large fat-fryer with water instead of oil in the tank. Units are available
from 75 up to 600 lbs per hour steam output, 100,000 to 800,000 BTUs per hour
gas input.
Carel USA manufactures and distributes a full line of industrial and commercial humidifiers and OEM controls for the HVAC industry. With over 30 years of experience, the Carel line includes steam, air/water atomizing, high pressure water atomizing, electrode, electric element, gas fired and direct steam humidifiers for printing, static control, museums, libraries, hospitals and many other applications.
More on Carel USA
Armstrong International
Reduce your operating costs through significant energy savings, compared to electric humidifiers, with the GFH Gas-Fired HumidiClean Humidifier from Armstrong. HumidiClean's innovative Ionic Bed Technology reduces your operating costs even more by eliminating the labor required by a surface skimmer. The GFH uses natural gas or propane for economical operation.