| Overview
Natural Gas and
Coal Cofiring is a technology that uses gas burners inserted into the boiler in
a way that allows both coal and natural gas to be burned at the same time. The
main advantages are environmental and load control. Gas burners can be turned
up and down very easily and quickly compared to coal, especially, stoker type
coal boilers. Gas burners can also be used for pilot burners to start the flame,
and for flame stabilization at low load factors.
Application
Large coal and
bio-mass boilers with a need to improve emissions and/or control problems are
good candidates for the addition of natural gas burners. GRI did a substantial
amount of research and co-funded several pilot installations in the mid-1990s.
Their work identified the gas cofiring advantages as falling into two general
categories of Environmental and Operational. Because natural gas is more expensive
than coal, it does not compete on a BTU basis; there must be some other need to
justify a cofiring system.
Environmental Benefits
- Opacity Reduction,
especially at start-up and turn-down
- NOx Reduction
- SOx Reduction
Operational
Benefits
- Improved Turn-down
and easier start-up
- Improved Load
following
- Recovered Derate
(if capacity was lost due to environmental or coal system limitations)
- Fuel Flexibility
- Standby Reserve
(quicker response time)
- Safety (cleaner
burning, less carbon/soot build-up)
- Reduced Maintenance
- Seasonal gas
usage
Burner
Sizing and Economics
Natural gas burners
are typically sized for 30 - 50% of total boiler capacity, and generally use 2
or 4 burners located in corners of the fire box. The gas burners will typically
fire at 5 - 15% of boiler capacity, depending on their design and needs of the
boiler. For example, if used for opacity control, when the boiler is at high-fire,
very little gas is needed; however, at start-up and low-fire conditions, a very
high percentage of natural gas is required. Burners are measured in millions of
BTUs and in MCF/Hour of usage. Annual loads can be substantial.
The burner cost
is not substantially affected by its gas input rating. The total cost of the project
is mostly affected by the total number of burners to be used and the retrofit
cost of the fire box to install them. For example, if technically feasible, 2
burners rated at 75% of boiler capacity is less expensive than 4 burners with
a total boiler capacity of 30%.
Payback is generally
measured in months, not years, and is NOT on a fuel cost BTU basis. Since gas
is likely to always be more expensive than coal or any other bio-mass fuel, payback
costs are considered against the costs of a bag house or other emissions control
system. In some cases, it may be the ONLY way the boiler can be fired and meet
emissions requirements.
For more information
see GTI's website www.cofire.com
Source: Energy
TechPro
 
|